Modeling of PV-STATCOM in a Grid-Connected Solar PV Plant for Voltage Regulation at the Point of Common Coupling

Authors Shankar Singh Thakuri, Sandeep Dhami, Menaka Karki, Basant Raj Tiwari

Abstract

Weak medium-voltage feeders often suffer from low voltage, and regulating this with dedicated devices such as static synchronouscompensators (STATCOMs) is costly. Meanwhile, grid-connected photovoltaic (PV) plants generally dispatch power at unity powerfactor such that the reactive-power capability of their inverters remains unused by day and the whole inverter remains idle at night.PV-STATCOM offers a solution by operating the existing inverter as a STATCOM, without the installation of new hardware. Thispaper studies a 10 MW two-stage PV plant, modeled on the Pure Energy Limited installation in Banke, Nepal, operated as aPV-STATCOM to regulate the voltage at its 33 kV point of common coupling (PCC). An electromagnetic-transient model of theplant and its controller was developed in MATLAB/Simulink. Under conventional daytime operation, the PCC voltage settles slightlybelow the normal band, and a large inductive load drops it to about 0.8 pu, by day as well as by night. As a PV-STATCOM, theplant regulates the voltage to its nominal value of 33 kV within a fraction of a second and maintains it there for as long as the loadremains connected. During the daytime, it continues to export power, only reducing its output by about 12% during the disturbance.At night, the idle plant provides the same support using about 70% of its rating while importing only its losses. After the addition offault ride-through control, the plant stays connected through a 150 ms three-phase grid fault, giving priority to reactive current andraising the PCC voltage during the fault by about 0.15 pu. Thus, the results justify the use of a utility-scale PV plant to providevoltage regulation day and night, and voltage support during grid faults, through a change of its control software alone.

Session EL2: Power Systems and Energy Technologies 2026-11-28
1169 EE
Presentation Confirmed
Vulnerability Assessment of Power System Network Using Centrality Measures

Authors Sajan Bahadur Aidi, Sandeep Dhami

Abstract

Increasingly complex and interconnected power system at this modern times have integration of varieties of distributed energyresources because of which there is a need for the analysis of network through fast and efficient method. At this era of electricalpower system development, grids are found to be decentralized and have high load topologies as a result of which the powersystem network becomes more vulnerable to N-1 contingencies and cascading failures caused by the loss of critical components.Though traditional power flow-based contingency analysis is electrically accurate, it requires exhaustive simulation of every possibleline or bus outage and becomes computationally expensive when the network gets larger. This study analyses a graph-theoreticscreening framework [1] in which the power system is modeled as a graph of buses (nodes) and transmission lines (edges) and thenetwork components are ranked on the basis of three centrality: closesness centrality, between ness centrality and current flowbetween ness centrality identifying structurally critical buses before detailed contingency simulations are run. The three centralitiesi.e. closeness centrality and between ness centrality, which are purely topological and assume power flows only along shortestpaths, and current-flow between ness centrality, which is electrically grounded are implemented and compared. The methodologyapplied in this paper was first validated manually using 5 bus Kaski substation network using the line reactance as distancefollowed by New England system IEEE 39 bus and finally the practical Integrated Nepal Power System INPS 118 bus network inMATLAB/MATPOWER. Most of same must critical buses in each system were shown by all three measures: Bus 16 in the IEEE39-bus system with closeness centrality 18.91, normalized betweenness centrality 0.51, normalized current-flow betweennesscentrality 0.56 whereas Bus 65 in the INPS. Similarly, Buses 17, 14, 3, and 15 also ranked consistently high in the 39-bus system,while pendant buses such as Buses 30–38 recorded zero betweenness and current-flow between ness since they lie at the end ofthe main power-transfer route. But the ranking diverged beyond the top tier in the manner that current-flow between ness rankedbuses carrying current over parallel paths higher such as that of Buses 6 and 26 in the 39-bus system; Buses 79 and 83 in theINPS and the divergence become greater as the network became more meshed and topologically bigger. From the study, it canbe concluded that closeness and between ness centrality serve as inexpensive first-pass screens for the few most critical buseswhile current-flow between ness is needed for a complete, electrically grounded priority list to move towards detailed contingencyanalysis and grid-hardening decisions.

Session EL2: Power Systems and Energy Technologies 2026-11-28
1171 EE
Presentation Confirmed
Optimal Size and Location of Solar PV Using Particle Swarm Optimisation for Voltage Profile Improvement and Power Loss Reduction “A Case Study of the Airport Feeder, Bhairahawa, Nepal”

Authors Rabindra Kumar Yadav

Abstract

The voltage drop and power loss in long distribution feeder problem occurs as increase demand. The optimal placement of (photovoltaic) PV can improve voltage profile and power loss reduction of distribution feeder. This study analyze the optimal photovoltaic (PV) impact analysis on Gautam international airport feeder. The 11 kV feeder of Bhairahawa Distribution and consumer (DCs) with 19.77 km of line length, 53 distribution transformer has connected and supplying 5.85 MW and  2.74 MVAR in summer season and 4.92 MW, 2.30MVAR in winter season . The feeder was modelled in DIgSILENT PowerFactory using line and each distribution transformer was assumed as one bus. Summer and winter season load has taken and varying with 80%, 100% and 120% load to perform load flow analysis before PV placement. Particle swarm optimisation (PSO) algorithm in MATLAB function used for optimal size and location of PV to achieve voltage limits within 0.95 p.u. to 1.05 p.u. Three units of PV at buses 19, bus 32 and bus 43 with total capacity 2.919 MW. The minimum bus voltage was 0.926 p.u. at bus 47 during summer season improved to 0.967 p.u. and 62.5 % power loss reduced. The minimum voltage 0.936 p.u. at bus 47 during winter season improved to 0.978 p.u. and 68.18 % of power loss reduced.

Session EL1: Power Distribution Planning and Optimization 2026-11-28
1176 EE
Presentation Confirmed
Design and Performance Evaluation of a PI--SMC-Controlled Boost PFC-Fed Wireless Power Transfer System with Integrated CC--CV Charging

Authors Archana Ghimire, Basanta Kumar Gautam, Lalit Bikram Rana

Abstract

This paper presents the design and simulation-based performance evaluation of a single-branch wireless power transfer (WPT) charging system integrating a proportional–integral and sliding-mode-controlled (PI–SMC) boost power factor correction (PFC) converter, a full-bridge inverter, a series–series (SS)-compensated resonant link, and receiver-side constant-current–constant-voltage (CC–CV) charging regulation. The proposed architecture is modelled and evaluated in MATLAB/Simulink to investigate grid-side power quality, DC-link voltage regulation, wireless energy transfer, and charging performance. The PI–SMC-controlled boost PFC converter maintains the DC-link voltage at 320 V while shaping the grid current, achieving a power factor of approximately 0.99994, compared with 0.80 without PFC. On the receiver side, the CC–CV controller regulates the charging current around its 11.4 A reference during constant-current operation and maintains the output voltage at the 320 V reference during constant-voltage operation. Furthermore, the system performance evaluation is carried out at three operating points corresponding to 120%, 100%, and 80% load demand along the CC–CV charging profile. The respective output powers are approximately 3000 W, 3550 W, and 2900 W, with conversion efficiencies of 88.1%, 91.0%, and 93.9%. The simulation results demonstrate the ability of the proposed integrated architecture to enhance grid-side power quality while providing resonant wireless energy transfer and regulated CC–CV charging under various load scenarios.

Session EL2: Power Systems and Energy Technologies 2026-11-28
1178 EE
Presentation Confirmed
Coordinated Active and Reactive Power Control Strategy for Voltage Regulation in Low-Voltage Distribution Networks with High PV Penetration

Authors Saphal Sigdel

Abstract

High photovoltaic (PV) penetration in low-voltage distribution networks causes voltage violations, because reverse power flow meets a resistance-dominated line impedance. This paper presents a coordinated active-reactive power control strategy that keeps the voltage within the ±10% band of IEC 60038 while minimizing the curtailed generation. The controller operates in three modes based on the locally measured voltage: during overvoltage it reduces active power and absorbs reactive power, during undervoltage it injects reactive power, and otherwise it operates at unity power factor. A coordination coefficient divides the required voltage correction between the two control variables. The strategy was tested on a 400 V, 2 km feeder with an R/X ratio of 7.73. Compared with curtailment-only control, it reduces the curtailed energy by 29 % to 96 %, depending on the penetration level, and by 62 % over a full day at 30 kWp, measured at the point of common coupling. Reactive-only control loses compliance above 26 kWp and does not recover it at higher penetration, which confirms that transmission-style reactive compensation is ineffective on resistive feeders. The coordination coefficient was validated against an exhaustive search that does not use the analytical expression. It remained within about 0.5 percentage points of the best fixed coefficient at every operating point, with a slightly conservative bias. On this feeder, the voltage rises with injected reactive power only up to about 18 kvar and falls beyond it, because the resistive drop caused by the reactive current exceeds the reactive voltage rise. The undervoltage branch is therefore limited by tracking the peak of the local voltage-reactive power characteristic. Finally, the reactive current increases line losses, so the benefit measured at the grid end of the feeder is smaller than that measured at the customer meter.

Session EL1: Power Distribution Planning and Optimization 2026-11-28
1186 EE
Presentation Confirmed
Virtual Synchronous Machine Control of an Islanded Grid Forming Inverter Under a Load Step and a Line to Ground Fault

Authors Dipesh Poudel, Bijaya Sapkota, Swagat Gautam, Kusum Upadhyay, Sandeep Dhami

Abstract

Inverter based generation stores no rotating energy, so as it replaces synchronous generators, the same power imbalance changes the system frequency faster. Grid forming inverters set the network voltage and frequency themselves, and the virtual synchronous machine  does so by solving the swing equation of a synchronous generator in its control. This paper identifies which part of such a controller shapes each response when the inverter is the only source of an island. A dq-frame VSM with cascaded voltage and current loops is modelled in MATLAB/Simulink and tested under a 50% load step and a one cycle single line to ground fault. The island remains stable in both cases. After the load step the frequency dips, overshoots once and returns to within 5 mHz of 50 Hz in about 0.2 s; because the load fixes the power of a single source, this response is set by the swing equation gains and the inner loop transient, not by stored energy. During the fault the negative sequence appears in the dq frame as a 100 Hz ripple that the PI loops cannot reject, so the active power and the d-axis voltage oscillate until the fault clears, the power peaking at about 2.2 times its pre-fault value. After clearing, the signals recover in the order of the control cascade: the voltage within about 35 ms, the power within about 40 ms and the frequency last. Fault ride through of an islanded VSM therefore depends on negative sequence control and current limiting in the inner loops, not on the emulated inertia.

Session EL2: Power Systems and Energy Technologies 2026-11-28
1220 EE
Presentation Confirmed
Techno-Economic Assessment of a 1~MW/4~MWh Battery Energy Storage System for Peak Shaving and Hydropower Support in Nepal

Authors Suraj Shrestha, Amamul Haq, Nikhil Gautam, Ruveen Pathak

Abstract

The paper evaluates the technical performance and economic viability of a lithium iron phosphate battery energy storage systemoperating under Nepal’s industrial time of day tariff framework. by establishing a component level conversion loss model, the studyresolves an ac to ac round trip efficiency of 90.85 percent and evaluates peak demand reduction across representative distributionfeeder loads, revealing an energy constrained regime at smaller scales and a power constrained regime at larger scales, withreductions reaching 18.20 percent. baseline economic evaluation reveals that relying solely on energy arbitrage is financiallyunviable: an initial capital expenditure of 93.10 million NPR yields a simple payback period far exceeding the asset life, a net presentvalue loss of 68.05 million NPR, and a levelized cost of storage exceeding the peak discharge tariff. sensitivity analysis confirmsthat capital expenditure dominates net present value variability, with all tested scenarios remaining strictly negative. however,benchmarking initial capital expenditure to 64.91 million NPR combined with a policy supported discharge tariff restores commercialviability, achieving a discounted break even at 13 years and a positive net present value of 4.96 million NPR. ultimately, the findingshighlight that standalone storage projects require coordinated capital cost restructuring and supportive regulatory frameworks,rather than incremental cost tuning, to become economically feasible in hydropower dominated grids.

Session EL2: Power Systems and Energy Technologies 2026-11-28
1162 EE
Presentation Confirmed
OPTIMAL SIZING AND PLACEMENT OF DG AND CAPACITOR IN RADIAL DISTRIBUTION NETWORK USING DRIVING TRAINING BASED OPTIMIZATION (DTBO)

Authors Saroj Kumar Sah, Suraj Shrestha, Om Prakash Jaiswal

Abstract

"
The growing demand for electricity has raised concerns about power dissipation in distribution system. The power losses and low voltage issues are major problems in radial distribution system due to overloading and longer feeder length. To mitigate these losses, capacitors and distribution generations (DGs) particularly solar PV systems, are strategically placed within the system. This paper is committed to reduce power loss and improve voltage profile significantly, optimizing the placement of capacitor and distributed generation along the distribution feeder using a novel driving training based optimization. The application of forward and backward sweep method assists load flow analysis in distribution network with high R/X ratios, while the incorporation of DTBO within MATLAB identifies optimal location and size for and DG. Test outcomes conducted on an IEEE 69-bus test system and is further applied to real distribution network of the 11 kV Piradi feeder of NEA Janakpur Distribution Center sustaining the approaches effectiveness in mitigating power losses and improving the voltage profile.
"

Session EL1: Power Distribution Planning and Optimization 2026-11-28
1163 EE
Presentation Confirmed
Optimal Coordination of Tap Changers, Capacitors, and PV Reactive Power for Voltage Control in Distribution Networks

Authors Suman Gnawali

Abstract

"
The increasing integration of intermittent renewable energy sources, particularly solar photovoltaics (PV), into distribution networks presents significant challenges to voltage stability and power quality. Traditional voltage control devices such as on-load tap changers (OLTCs) and capacitor banks are mechanical and suffer from excessive wear due to frequent operations under high PV penetration. This paper proposes a centralized coordinated control strategy that simultaneously optimizes the settings of tap-changing transformers, switched shunt capacitors, and the reactive power capability of PV inverters. A weighted multi-objective optimization framework is developed to minimize voltage deviations from the nominal value (1.0 p.u.), reduce active power losses, and limit mechanical operations on traditional devices. The Grey Wolf Optimization (GWO) algorithm is used as the primary solver, while Particle Swarm Optimization (PSO) and Harmony Search (HS) are implemented for comparative performance evaluation. The methodology is validated on the Janakinagar 53 bus feeder using realistic half-hourly load and PV generation profiles. Three control cases are investigated: (I) tap changers only, (II) tap changers + capacitors, and (III) full coordination (tap changers + capacitors + PV reactive power). Final results demonstrate that full coordination in Case III significantly improves voltage regulation and reduces system losses while substantially lowering mechanical wear compared to conventional approaches.
 
"

Session EL1: Power Distribution Planning and Optimization 2026-11-28
1165 EE
Presentation Confirmed
Transient Stability of Power System Networks Incorporating Virtual Synchronous Generators

Authors Rajan Yadav, Binod Sharma, Prabin Kumar Mahato

Abstract

Replacing synchronous machines with converters removes the rotating mass on which conventional transient stability depends.Virtual Synchronous Generators (VSGs) restore that behaviour in software by solving the swing equation inside a grid-formingconverter, but the emulation holds only while the converter can supply the current its controller demands. Published work identifies converter current limiting as the mechanism that sets the stability boundary. This paper tests that expectation on the IEEE 9-bus benchmark, in which two of three synchronous generators are replaced by VSG units with an explicit current saturation algorithm.A detailed MATLAB model is cross-checked against an independently written reduced-order multi-machine program that solves the load flow, reduces the network to the generator internal nodes and integrates the swing equations directly. Three results are reported. First, at the parameters as built the network withstands a three-phase fault of 753 ms, which is far more robust than anticipated; the converters are rated well above their dispatch, so the inertia they emulate, referred to the system base, is large. Second, the critical clearing time is strongly and almost linearly dependent on the virtual inertia constant, falling from 753 ms to 81ms as that constant is reduced from 4 s to 0.1 s, whereas the current limiter never engages in any case that decides an outcome. Third, a STATCOM at a voltage-weak bus raises the critical clearing time at a representative low-inertia operating point from 281 ms to 608 ms and reduces peak kinetic energy by 86 per cent, acting after fault clearance rather than during the fault. The ratio of converter rating to dispatch, rather than VSG control in general, decides whether emulated inertia or current limiting governs stability.

Session EL1: Power Distribution Planning and Optimization 2026-11-28